Here is how ECCO2’s expertise in Monitoring, Optimisation, and Performance Gap Solutions helped this building perform at its best.
ECCO2 Monitoring: Uncovering Issues
- Incorrect switch position on the emergency electric heater prevented the heat pump from heating water, leading to inefficiencies.
✅ Result: A 40% reduction in electricity consumption for the commons after correction. - Misconfigured switchover between cooling and heating caused low indoor temperatures at the start of the heating season.
✅ Result: Resolved remotely in just 5 minutes.
ECCO2 Performance Gap & Optimisation: Closing the Gap
Our analysis revealed a gap between planned and actual heating energy consumption:
- Planned Energy Demand: 22 kWh/(m²*a)
- Actual Consumption (without optimisation): ~27 kWh/(m²*a)
- Post-Optimisation Performance: ~23 kWh/(m²*a)
This is the value of ECCO2 Monitoring: uncovering hidden inefficiencies, while ECCO2 Performance Gap & Optimisation identify and bridge the gap between design and reality.
A close collaboration made it possible. Thanks to the regional electricity provider, heating cost accounting team, heat pump supplier, property manager, concierge, and heating contractor, we identified and resolved inefficiencies quickly and effectively.
Monitoring, Performance Gap, and Optimisation are at the core of what we do, and this recent project demonstrates how these solutions work together to deliver real impact.
Curious about what ECCO2 could do for your building? Let’s talk!